Flowline EchoPro® LR11 Liquid Level Sensor Transmitter w/26 GHz Pulse Radar, 32.8 ft. Range, Intrinsically Safe

SKU:
FLWLR11542100
Manufacturer:
Flowline
Size:
1 1/2 in. Male NPT
Product Type:
Radar Liquid Level Sensor
Material:
PFA
Weight:
8.00 LBS
$1,802.63
Adding to cart… The item has been added
EchoPro® LR11 intrinsically safe 26 GHz pulse radar level transmitter provides continuous level measurement up to 32.8 ft. (10m) range with a 4-20 mA signal output and Hart digital signal output. The sensor is configured by a integral push button display module or HART communicator. This non-contact liquid level sensor is for chemical or water storage applications in above grade metal or reinforced concrete tanks or below grade tanks of any material. This sensor is for easy process conditions with corrosive media, light agitation, condensation or vapor and installation in a low-profile tank adapter or flange fitting. Applications include chemical bulk storage and tanker trucks.

Features

  • Configuration via push button display or HART communicator
  • IP67 stainless enclosure with polycarbonate display window
  • LCD displays level in feet or meters with percent of span bar
  • Optional display mode indicates the echo signal return curve
  • Fail-safe diagnostics with selectable signal fail-safe outputs
  • Recognition, storage and rejection of false echo signal returns
  • 26 GHz. pulse radar is unaffected by vapor or condensation
  • 12 in.(30cm) dead band enables utilization of the entire sump

Specifications

  • 1 1/2 in. NPT
  • Range: 12 in. to 32.8 ft. (30 cm to 10m)
  • 26 GHz frequency
  • Accuracy: ± 5mm
  • PTFE transducer
  • HART 7 & 4-20mA output
  • Pressure: -14.5 to 43.5 PSI (-1 to 3bar)
  • Dead band: 12 in. (30 cm)
  • Configuration: Push button, HART 7
  • Display: LCD, dot matrix
  • Display units: feet and meters
  • Display bar: Percent of span
  • Display graph: Echo signal curve
  • Memory: Non-volatile
  • 22° beam angle
  • Supply voltage: 21.6 to 26.4V DC
  • Max. Consumption: 22.5 mA
  • Signal output: 4-20 mA, two-wire, HART 7
  • Signal invert: 4-20 mA, 20-4 mA
  • Temp. comp: Automatic
  • Process temp.: -40° to 266° F (-40° to 130°C)
  • Storage temp.: -40° to 176° F ( -40° to 80° C)
  • Enclosure material: 316 Stainless Steel w/Silicone Gasket
  • Display window: Polycarbonate
  • Conduit entrance: (1) 1/2 in. NPT connector
  • Classification: Intrinsically safe
  • Certification: FCC
  • Complies to CE, RoHS

Downloads

Datasheet (PDF Download)

Quick Start (PDF Download)