null

Dixon ADS A210 Spillguard 120 / 240 VAC Monitor w/ By-Pass Timer

SKU:
DXA210B120
Manufacturer:
Voltage:
120 / 240 VAC
Weight:
5.00 LBS

Call for pricing: (800) 333-3331

Dixon ADS A210 Spillguard 120 / 240 VAC Monitor w/ By-Pass Timer

Dixon ADS A210 Spillguard 120 / 240 VAC Monitor w/ By-Pass Timer

SKU:
DXA210B120
Manufacturer:
Voltage:
120 / 240 VAC
Weight:
5.00 LBS

Call for pricing: (800) 333-3331

An automatic, high level shutdown system for tank cars, tank trucks, barges, and ships. Prevent spills, personal exposures, and overloading. Suitable for open and closed dome.

Features

  • Rugged, explosion proof, weather, chemical and corrosion resistant
  • LED status lights visible through glass cover
  • Inserts into tank through standard 1/2" NPT fitting
  • Probe can be portable or permanently installed in the vessel
  • Laser engraved graduated rod with 1/4 graduations
  • Probe-to-controller cable protected by stainless steel interlocking armor sheath and heavy duty latching connectors at both ends
  • Fail safe design, unit trips in the event of an open or shorted cable or loss of power
  • Controller housing NEMA 4X, Nema 7, Explosion Proof, Class I, II, Groups B, V and D
  • Choice of capacitance, conductivity, ultrasonic, temperature or float sensors
  • Output relay contacts 2 form C (2PDT) rated 2 amps at 120/240 VAC, 1 form C (SPDT) with optional latching circuit and reset switch
  • Output relay de-energizes on high level, broken or shorted sensor cables or loss of power
  • Sensor excitation open circuit voltage 8 VDC, short circuit current 8MA with built-in FM approved barrier

Specifications

  • Sensor suitable for Class I, II, III, Div 1, Groups A, B, C and D when used with supplied controller and cable lengths of 10,000' or less
  • Cable connectors designed for repeated mating meet IP 65 mechanical and environmental specifications
  • Temp: -14°F to 212°F (-26°C to 100°C)
  • Wetted Materials: 316 stainless steel and PTFE
  • Max Pressure: 50 PSI with standard fitting
WARNING: This product may contain a chemical known to the State of California to cause cancer & reproductive harm. For more information, go to www.P65Warnings.ca.gov.