Dwyer Series MS Magnesense® Differential Pressure Transmitter w/LCD & Wall Mount, 5V Output & 12V Input

SKU:
Please choose an option below
Manufacturer:
Dwyer
Product Type:
Pressure Transmitter
Size:
3/16 in. ID tubing.
Pressure:
1 PSI
Weight:
5.00 LBS
$182.27 - $207.51
Adding to cart… The item has been added

The Series MS Magnesense® Differential Pressure Transmitter is an extremely versatile transmitter for monitoring pressure and air velocity. This compact package is loaded with features such as: field selectable English or metric ranges, field upgradeable LCD display, adjustable dampening of output signal (with optional display) and the ability to select a square root output for use with Pitot tubes and other similar flow sensors. Along with these features, the magnetic sensing technology provides exceptional long term performance and enables the Magnesense® transmitter to be the solution for a myriad of pressure and flow applications. applications: Building pressure monitoring, duct pressure monitoring, fan velocity measurement, zone differential pressure monitoring, filter condition monitoring.

Features

  • Field selectable English or Metric ranges
  • Field upgradeable LCD display
  • Adjustable damping of output signal (with optional display)
  • Ability to select a square root output for use with pitot tubes and other similar flow sensors.

Specifications

    • Service: Air and non-combustible compatible gases.
    • Accuracy: ±1% for 0.25" (50 Pa), 0.5" (100 Pa), 2" (500 Pa), 5" (1250 Pa), 10" (2 kPa), 15" (3 kPa), 25" (5 kPa) ±2% for 0.1" (25 Pa), 1" (250 Pa) and all bidirectional ranges.
    • Stability: ±1% FS/year.
    • Temperature Limits: 0 to 150°F (-18 to 66°C).
    • Pressure Limits: 1 psi maximum, operation; 10 psi, burst.
    • Power Requirements: 10 to 35 VDC (2-wire); 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire).
    • Output Signals: 4 to 20 mA (2-wire); 0 to 5 V, 0 to 10 V (3-wire).
    • Response Time: Field adjustable 0.5 to 15 sec. time constant. Provides a 95% response time of 1.5 to 45 seconds.
    • Zero & Span Adjustments: Digital push button.
    • Loop Resistance: Current output: 0-1250 Ω max; Voltage output: min. load resistance 1 kΩ.
    • Current Consumption: 40 mA max.
    • Display (optional): 4 digit LCD.
    • Electrical Connections: 4-20 mA, 2-wire: European Style Terminal Block for 16 to 26 AWG. 0-10 V, 3-wire: European Style Terminal Block 16 to 22 AWG.
    • Electrical Entry: 1/2" NPS Thread.
    • Accessory: Cable Gland for 5 to 10 mm diameter cable.
    • Process Connection: 3/16" (5 mm) ID tubing. Maximum OD 9 mm.
    • Enclosure Rating 4X (IP66).
    • Mounting Orientation: Diaphragm in vertical position.
    • Weight:8.0 oz (230 g).

Downloads

Product Manual (PDF Download)